Integration of UPQC in Grid Connected PV System
by Power Angle Control Scheme
KATHA MUTHU.M
M.Tech – Power System Engineering,
PRIST Deemed University, Madurai, Tamilnadu
Abstract -The quality of electric power is greatly affected by the
proliferation of non-linear loads in electrical energy processing
applications like switched mode power supplies, electric motor
drives, battery chargers, etc., The custom power devices like
UPQC has gained more importance in power quality arena as it
gives the best solution for all power quality issues. UPQC is the
combination of both shunt and series active power filters
connected through a common DC link capacitor. The shunt
active power filter is the most corrective measure to remove the
current related problems, power factor improvement by
supplying reactive power and regulates DC link voltage. The
series APF acts as controlled voltage source and corrects voltage
related problems, like sag or swell, flickering, harmonics, etc.,.
As a combination of both of these, UPQC improves service
reliability. In the present work, shunt inverter control is based on
modified active ,reactive (p-q) power theory, uses High
selectivity filter (HSF) for reference current generation. The
series APF uses Power Angle Control (PAC) scheme for
compensating sag/swell, interruption and voltage related
problems along with sharing a part of load reactive power
demand with shunt APF and thus ease its loading and makes the
utilization of UPQC to be optimal. The topology uses three
phase three leg inverters for both shunt APF and series APF. The
gating signals were generated using Hysteresis controller. The
output of High step-Up DCDC Converter is used to work as DC
voltage source for both APFs. The input voltage for the
converter is provided by Photo Voltaic array incorporated with
P&O MPPT technique. The use of high step-up DC-DC
converter is for high voltage gain with better efficiency. The
present topology avoids the PLL in shunt active power filter.
Keywords: Power Angle Control, power quality, UPQC
I.INTRODUCTION
The term power quality got significant importance in
the electric power industry. The increasing application of
electronic equipment and distributed generation has led to the
Degradation of power quality by injecting harmonics, flicker and
voltage imbalance into the system. In addition, switching of
capacitor banks, lightning strikes on transmission lines and
various faults on the network also creates the power quality
issues such as transients, voltage sag or swell, interruptions,
etc.,.. The equipment which is increasingly susceptible to the
variations in Power Quality is termed as Sensitive Equipment or
Sensitive Load [4]. For proper load operation, it requires pure
sinusoidal voltage. With fast growing digital technology, the
devices that depending upon volatile memory chip for storages
are increasing and these are potentially at risk from power
quality events. To achieve this pure sinusoidal voltage and to
meet the power quality standards, it is necessary to use some
compensation techniques. Previously passive filters using tuned
LC components have been used to mitigate the harmonics,
which are low in cost, simple in configuration. But this has
drawbacks of fixed compensation, bulky in size and creates
resonance problems. Hence a modern solution is found in the
form of active power filtering. The shunt APF is suitable for
suppressing source current harmonics and the series APF is
suitable to compensate source voltage imperfections. The power
electronic controllers used in distribution system for the purpose
of supplying a level of reliability or power quality, which is
essentially required by sensitive load, is termed as custom power
devices [4]. These devices have the ability to perform voltage
regulation and current interruption functions within the
distribution system and hence it can be treated as power
conditioning device.
Page 2 of 7
European Journal of Business &
Social Sciences
Available at https://ejbss.org/
ISSN: 2235-767X
Volume 07 Issue 04
April 2019
Available online: https://ejbss.org/ P a g e | 2066
II.POWER QUALITY
A sinusoidal signal of constant amplitude and of single
frequency which is constant is characterized as an ideal voltage
or current signal. Further it is required to maintain both voltage
and current in phase. Hence the quality of voltage quality or
current quality is the quality of voltage delivered to the
consumer or taken from the utility. Power quality problem is
nothing but the deviation of voltage/current from its ideal value.
Though the generator voltage is at or near pure sinusoidal, the
current passing through the load may create disturbance to it and
viz. voltage quality and current quality together is termed as
power quality. The process of supplying and grounding the
sensitive equipment with power such that the operation of such
equipment is satisfactory is nothing but power quality. Power
Quality has different meanings and significances according to
the requirement for which it has been defined. In the perspective
of designer or manufacturer, power quality is defined in a
manner that there should be no variation in voltage and no noise
generation in the grounding system. In view of utility engineer,
it is voltage availability or outage minutes. For the end users the
feasibility in using the available power for driving all kinds of
loads is termed as power quality. So a nonstandard voltage,
current or frequency that causes mal operation of end user
equipment is termed as power quality problem. Although the
entire power system has impact on power quality, most of the
problems occur in distribution system itself. The power quality
became significantly worse at points where the loads are
connected to the distribution grid
Power Quality Problems
1. Harmonic Distortion
2. Voltage Dips / Sags, and Surges / Swells
3. Unbalance
4. Flicker
5. Transients
III.UNIFIED POWER QUALITY CONDITIONER
The Unified Power Quality Conditioner is a custom power
device that is employed in the distribution system to mitigate the
disturbances that affect the performance of sensitive and/or
critical load [1]. It is a type of hybrid APF and is the only
versatile device which can mitigate several power quality
problems related with voltage and current simultaneously
therefore is multi functioning devices that compensate various
voltage disturbances of the power supply, to correct voltage
fluctuations and to prevent harmonic load current from entering
the power system. Fig. 1 shows the system configuration of a
single-phase UPQC. Unified Power Quality Conditioner
(UPQC) consists of two IGBT based Voltage source converters
(VSC), one shunt and one series cascaded by a common DC bus.
The shunt converter is connected in parallel to the load. It
provides VAR support to the load and supply harmonic currents.
Whenever the supply voltage undergoes sag then series
converter injects suitable voltage with supply [2]. Thus UPQC
improves the power quality by preventing load current
harmonics and by correcting the input power factor.
Block diagram of UPQC
Basic configuration of UPQC
The main components of a UPQC are series and shunt power
converters, DC capacitors, low-pass and high-pass passive
filters, and series and shunt transformers:
Series converter
It is a voltage-source converter connected in series with the AC
line and acts as a voltage source to mitigate voltage distortions.
It is used to eliminate supply voltage flickers or imbalance from
the load terminal voltage and forces the shunt branch to absorb
current harmonics generated by the nonlinear load. Control of
the series converter output voltage is usually performed using
sinusoidal pulse-width modulation (SPWM). The gate pulses
required for converter are generated by the comparison of a
fundamental voltage reference signal with a high-frequency
triangular waveform.
Shunt converter
Page 3 of 7
European Journal of Business &
Social Sciences
Available at https://ejbss.org/
ISSN: 2235-767X
Volume 07 Issue 04
April 2019
Available online: https://ejbss.org/ P a g e | 2067
It is a voltage-source converter connected in shunt with the same
AC line and acts as a current source to cancel current distortions,
compensate reactive current of the load, and improve the power
factor. It also performs the DC-link voltage regulation, resulting
in a significant reduction of the DC capacitor rating. The output
current of the shunt converter is adjusted using a dynamic
hysteresis band by controlling the status of semiconductor
switches so that output current follows the reference signal and
remains in a predetermined hysteresis band.
IV.PHOTO VOLTAIC POWER GENERATING SYSTEM
Photo voltaic power generation uses solar cells to
convert solar irradiation into electrical energy. A grid connected
PV system converts light energy into electrical energy directly
and thus it mainly reduces the energy extracted from the
electrical utility. The development in power electronics and
material science has helped to develop compact but efficient
systems to withstand the high power demand. The PV cell
exhibits nonlinear I–V and P–V characteristics. The series
connected solar cells, which are basic building blocks of it,
forms a PV module. These PV modules are connected either in
series or in parallel depending upon its power rating forms a PV
array. The maximum power produced varies with temperature
and irradiance. Each cell has different current and voltage
maximum positions as these have non-linear characteristics. But
the power maximum point is unique, which mainly depends
upon Temperature and Irradiation. To track that maximum
power point, it is essential to use MPPT algorithm. The
maximum power point tracking (MPPT) algorithm is used to
extract the maximum power from PV panels from instantaneous
variations of irradiation, temperature and PV module
characteristics
P&O MPPT Technique
Maximum Power Point Tracking technique uses maximum
power transfer theorem, which states that, the output power is
maximum when thevinins impedance of circuit is equal to the
load impedance. Hence tracking the maximum power point is
nothing but tracking the impedance matching point. There are
many MPPT techniques available like perturb and observe
technique, Perturb and Observe (P&O), Incremental
Conductance method, Neural networks method, Fractional open
circuit voltage method, Fractional short circuit current method,
Fuzzy logic method [17], etc.,. The suitability of technique
depends on different parameters like cost, application, dynamic
performance and ease of implementation. Here we considered
P&O MPPT technique for our application. The P&O MPPT uses
only one voltage sensor. Hence it is cost effective and easy to
implement. The P&O MPPT algorithm states that when the
power converter operating duty cycle varies and the PV array
voltage is perturbed by a small increment and if the resulting
change in power, ΔP is positive, then it means that it is going in
the direction of MPP. Hence it keeps on perturbing in the same
direction. If ΔP is negative then it means it is going away from
the direction of MPP and the sign of perturbation is to be
changed. Thus this method uses the sign of perturbation and sign
of change in power to vary the duty cycle to be operated to track
the MPPT.
V.POWER ANGLE CONTROL SCHEME
The rating of series APF used in UPQC depends upon
the maximum percentage of sag/swell that it should compensate.
But these are of small duration issues. But the shunt APF
operates as long as the non-linear currents are drawn from the
source. It supplies the reactive power continuously, which leads
to increased utilization of it compared to series APF. The power
angle control scheme is mainly used to increase the utilization
factor of series APF without causing any additional burden on it.
Here the series APF is used to share a part of load reactive
power demand along with compensating voltage sag/swell by
creating a power angle difference between source voltage and
load voltage. The compensation of sag can be done by active
power approach or reactive approach or by both of these in
UPQC. Here this scheme uses both active and reactive power
approach to compensate the sag/swell by maintaining a constant
load voltage. The operation is better explained using the phasor
diagram shown in below