Estimation of Frequency in Power System Network

Using Linear and Nonlinear Techniques

RAMESH.D.

M.Tech – Power System Engineering,

PRIST Deemed University, Madurai, Tamilnadu

Abstract –

In an electrical power system frequency is an important

parameter. The frequency of operation is not constant but it

varies depending upon the load conditions. In the operating,

monitoring and controlling of electric device power system

parameters are having great contribution. So it is very important

to accurately measure this slowly varying frequency. Under

steady state conditions the total power generated by power

stations is equal to system load and losses. Frequency can

deviate from its nominal value due to sudden appearance of

generation-load mismatches. Frequency is a vital parameter

which influences different relay functionality of power system.

This study was made to estimate the frequency of measuring

voltage or current signal in presence of random noise and

distortion. Here we are first using linear techniques such as

complex least mean square (LMS), least square (LS) and

recursive least square (RLS) algorithm for measuring the

frequency from the distorted voltage signal. Then comparing

these results with nonlinear techniques such as nonlinear least

mean square (NLMS), nonlinear least square (NLS), nonlinear

recursive least square (NRLS) algorithms. The performances of

these

Algorithms are studied through simulation.

Key words: Frequency, linear techniques, Non linear techniques

I.INTRODUCTION

Frequency in electrical power system is an important

operating parameter which is required toremain constant because

it reflects the whole situation of the system. Frequency can show

the activeenergy balance between generating power and load.

Therefore frequency is considered as an indexfor operating

power systems in practical. In power system frequency is not

constant but changes according to load condition. Ideally this

frequency should be constant, but due to noise, sudden

appearance of load–generation mismatches and increasing use of

nonlinear load, the frequency of operating system is not

constant. Component reactance change results due to deviation

in system frequency from its desired value which influences

different relay functionality of power system such as server

damage or reactive power reduction occurs in system devices.

So the frequency plays an essential role in operating, monitoring

and controlling of any power system device. Basically

digitalized samples of current or voltage signal are used for

available frequency estimation techniques. Generally, the

voltage signal is used for frequency estimation because it is less

contort than the line current. Considering the purely sinusoidal

power system voltage signal, the frequency can be defined as

time

between two zero crossing. However in practice, the measured

signals are available in the distorted form and many techniques

are available for estimation of the frequency. Further, many

power electronic equipment and arc furnaces etc. generate

disturbances in the power systems. Therefore it is necessary for

utilities to develop a realistic approach for measurement of

frequency in presence of noises. Since frequency variation is a

dynamic phenomenon, the conventional phasor estimation

techniques such as Discrete Fourier Transform (DFT), Least

Square (LS) and Kalman Filtering may not be appropriate for

achieving accurate frequency estimation under dynamic

conditions. Zero crossing technique, discrete Fourier transform,

phase lock loop, least square error; orthogonal finite impulse

response filtering, Kalman filtering and iterative methods are

some techniques in this area. Soft computing technique such as

genetic algorithm and artificial neural network are also use for

power system frequency estimation. Also for protection and

control of the power system devices it is essential to have a

knowledge of frequency, therefore it is necessary that how we

are estimating the frequency without significant delay. It is

therefore absolutely necessary to develop a realistic approach for

frequency measurement in presence of disturbances. This paper

represented estimation of frequency from a distorted voltage

waveform. By considering different situation of power system

the distortion of the system signal is further enhanced. An

algorithm used here are complex least mean square (LMS) using

three phase voltage signal, LS estimator and RLS estimator. The

first two estimators use batch processing and third one is online

Page 2 of 5

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 2033

processing. After that frequency estimation is done using some

nonlinear techniques such as

Nonlinear Least Mean Square (NLMS), Nonlinear Least Square

(NLS), and Nonlinear Recursive Least Square (NRLS). Then by

comparing the results of both linear and nonlinear method.

II.MATHEMATICAL ANALYSIS-LINEAR ESTIMATION

Power system frequency estimation

In power system with no loss performance is considered

for estimation. So it is significantto have a purely sinusoidal

voltage or current signal for a better power quality. But in

practical, itdecline due to over voltage, variation in frequency,

source type, under voltage, harmonics, generation load

mismatches. Therefore it is needed to estimate the frequency fast

and accurately for better power quality in presence of noise and

other disturbances .Digitized samples of supply voltage are used

in most of the methods for frequency estimation in power

system. Basicallyfrequency is defined as the time between two

zero crossing of a purely sinusoidal voltage. But in real, signals

are not available in pure form but are distorted. Hence there are

various methods for estimation of frequency. Zero crossing

detection and calculation of the number of cycles within a

particular time interval are some basic methods for finding the

frequency of a purely sinusoidal voltage waveform. Discrete

Fourier transformation (DFT), Kalman filtering, least square

error method, and iterative approaches (2, 6-11) are some of

well-known approaches in this area. In this chapter complex

Least Mean Square, Least Square and Recursive Least Square

has been implemented for power system frequency estimation.

Frequency Estimation Using Least Square (Ls) Algorithm

The least square is a standard method for the

approximate solution of over determined systems. Over

determined system is the system which having more no. of

equations than unknowns. Least square means the overall

solution minimizes the sum of the squared error. Least square

approach has two types linear and nonlinear depending on

whether residuals are linear in all unknowns or not. Linear least

square is the linear combination of the parameters i.e. it consists

of the linear equations. Linear least square has a unique solution

Simulation result of Least Square (LS) Algorithm:

The figure shows the plot of frequency Vs No. of

iteration. Here estimated frequency comes to be

50 Hz.

Least square method is used here for frequency estimation. By

using Matlab simulation has been done. This method has good

accuracy but convergence time is more. There is delay of 2 to 3

cycles in frequency estimation.

Frequency Estimation using Recursive Least Square (RLS)

Algorithm

A distorted power system signal with noise can be

given as,

y(t) A1 sin(0t 1) (t)

Simulation result of Recursive Least Square (RLS) Algorithm:

The Below figure shows the frequency estimated Vs

No. of iteration. In recursive least square method frequency

estimated comes to be 50 Hz. This method has a higher

convergence rate than the previous one. Also time required to

estimate the frequency is less with good accuracy.

Frequency Estimation using Least Mean Square (LMS)

Algorithm

The least-mean-square (LMS) algorithm simplification

of the gradient vector and its computation is done by modifying

the objective function. Due to its computational simplicity The

LMS algorithm, is widely used in various applications of

adaptive filtering. In order to construct a range for the

convergence factor the convergence characteristics of the LMS

algorithm are studied that will guarantee stability .The

convergence speed of the Least Mean Square algorithm is

dependent on the Eigen value spread of the input signal

correlation matrix. The LMS algorithm is mostly used algorithm

in adaptive filtering for lots of reasons. The main features are

less complexity, unbiased convergence in the mean to the

Whoops!
There was a problem loading this page. Retrying...

Page 3 of 5

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 2034

Wiener solution, proof of convergence in stationary environment

and stable nature.

Steps for Frequency Estimation using Least Mean Square (LMS)

Algorithm

1. Initialize A , , , , , R , W , f , 

2. Generate power system signal

3. Using initial values of the weight vector estimate the

discredited signal

4. Error=Actual signal – Estimated signal

5. Update the step size and auto correlation matrix

6. Update weight vector

7. Go to step 4, until final iteration is reached

8. Estimate the fundamental frequency

Simulation result of Least Mean Square (LMS) Algorithm:

Simulation result of Least Mean Square (LMS) Algorithm:

LMS algorithm is applied to estimate the fundamental frequency

from the sampled value of the phase voltage signal. Parameters

of algorithm are 0.010.018, Pinitial , r=0.99, =0.01

And value changes according to sampling instant.

Figure shows the simulation result obtained by

implementing the above described LMS algorithmic Matlab.

Here in graph step change in frequency is given and

performance is observed. From the figure it is seen that during

step change in frequency from 50 Hz to 49 Hz there is delay of

0.001second. Accuracy and speed of estimation is satisfactory

even in presence of noise and harmonics. Advantages of this

algorithm are simplicity in formulation and computational

efficiency

IV.MATHEMATICAL ANALYSIS-NONLINEAR

ESTIMATION

Power system frequency estimation using Nonlinear Least

Square (NLS) Algorithm

Nonlinear Least Square estimation is the approach used

for the estimation of Fundamental frequency. Here frequency is

estimated by minimizing the squared error between actual signal

and assumed signal. For the model y(k) is the actual signal,(k)

is the system structure matrix and (k) is vector of parameters to

be estimated.

Simulation result of Nonlinear Least Square (NLS) Algorithm:

Accuracy of the algorithm decides the robustness of the

1-D search. The typical behavior of the norm of error as a

function of frequency is shown in the figure below. Here the

search is carried out by varying the fundamental frequency 0 f in

the steps of 0.1Hz .True frequency is the frequency at which the

minimum of the curve occurred. For the frequency estimation

we considered a voltage waveform having 10% total harmonics

and additive random noise which was given as

Here 3.2 KHz is the sampling frequency used for computer

simulation and the fundamental frequency is taken as 50Hz. In

power system half-wave symmetry waveforms are very common

soit does not contain even numbered harmonics and triplen

harmonics. Triplen harmonics are the 3rd and multiple of

fundamental harmonics. Using above sampling frequency,

maximum 32 harmonics can be taken into consideration without

any aliasing, which is suitable for the any application of power

system environment. Using above voltage signal we estimated

the frequency by nonlinear least square technique by varying the

frequency of voltage signal from 48.5 to 51.5Hz. As seen by

below figure simulation result we found that minimum error

occurred at 50.1Hz which is the estimated frequency.