Dissolved Gas Analysis Technique Based

Assessment of High Voltage Power Transformer

BHUVGANESWARI . P

M.Tech – Power System Engineering,

PRIST Deemed University, Madurai, Tamilnadu

Abstract - Dissolved Gas Analysis (DGA) is a widely used

technique to estimate the condition of oil-immersed

transformers. The experimental results of the level and the

change in concentration of different combustible gases in the

insulating oil is a trustworthy diagnostic tool which can be used

as indicator of undesirable events occurring inside the

transformer, such as hot spots, electrical arcing or partial

discharge. The objective of this paper is mainly to analyse

available data from DGA, and investigate data that may be

useful in quantitative modeling of the transformer’s reliability.

Dissolved Gas Analysis (DGA) of transformer oil is the best

indicator of a transformer’s overall condition. It will provide

useful information about the condition of oil and help to identify

the type of fault in the transformer. Depending upon the location

of a transformer, its rating and the nature of its usage, some

dissolved gas analysis is to be scheduled which will be

appropriate for that transformer. The more critical the unit is the

more frequently it should be sampled. Hence DGA is mainly

performed in Power transformers.

I.INTRODUCTION

Power transformers play an important role in both the

transmission and distribution of electrical power. Since a fault in

a transformer can have a huge repercussion when failures occur,

and as the number of old transformers and of those that are

difficult to operate in overload conditions is on the rise, it is

important to detect incipient faults in a transformer and forecast

and prevent failures [17]. In operation, transformers are subject

to electrical and thermal stresses, which can cause the

degradation of the insulating materials. Generally the

degradation products are gases, which will get dissolve in the oil

entirely or partially. In the oil these gases are easily detected at

the ppm level by dissolved gas analysis. Dissolved gas analysis

(DGA) is a widely used most powerful method to detect

incipient faults on oil filled electrical equipment [16]. The

electrical equipment may be a transformer, a load tap changer or

a cable. When the mineral oil is subjected to high thermal and

electrical stresses, it decomposes and, as a result, gases are

generated. Different types of faults will generate different gases,

and the chemical analysis of these gases, performed through a

procedure called DGA (Dissolved Gas

Analysis), will provide useful information about the condition of

the oil, and help to identify the type of fault in the transformer.

DGA is performed accordance with ASTM D3612 or IEC

60567. There are different types of faults which can be detected

by DGA. The details about the faults are explained below

Partial Discharge (PD):

The temperature plays a less important role in the chemical

reaction occurring in the PD since the vapour temperature in the

discharge zone is not higher than 60-150°C. Hydrocarbon

cracking in the partial discharges occurs as a result of excitation

of molecules and their subsequent dissociation by collision with

high energy electrons, atomic hydrogen, ions and also free

radicals. It often generates large amounts of hydrogen. Example:

Discharges of the cold plasma (corona) type in gas bubbles or

voids, with the possible formation of X-wax in paper.

Discharges of Low energy (D1):

Partial discharges of the sparking type, inducing pinholes,

carbonized small punctures in paper. Low energy arcing results

in surface tracking of paper or the formation of small amount of

carbon particles in oil.

Discharges of High energy (D2):

Discharges in paper or oil, with power follow-through, resulting

in extensive damage to paper or large formation of carbon

particles in oil, metal fusion, tripping of the equipment and gas

alarms.

Thermal fault (T1):

These types of faults occur below . These are evidenced by

paper turning brownish (> 200 °C) or carbonized (> 300 °C).

Thermal fault (T2): These types of faults occur in between to .

These are evidenced by carbonization of paper, formation of

carbon particles in oil.

Thermal fault (T3):

Page 2 of 7

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 2019

The high temperature faults whose temperature is more than falls

in this kind of fault. These are evidenced by extensive formation

of carbon particles in oil, metal coloration (800 °C) or metal

fusion (>1000 °C).

Thermal & Electrical fault (DT): Sometime both thermal and

electrical fault occurs inside the transformer. These faults

accelerate the decomposition of dielectric fluid and solid

insulation

II.DETECTION TECHNIQUES OF DISSOLVED GASES

The DGA technique detects gas in parts per million

(ppm) dissolved oil by the use of gas extraction unit and a gas

chromatograph. The DGA analysis is performed in three steps:

1. Collection of Oil sample

2. Extraction of gases from the oil

3. Detection of gases

Collection of oil sample

The oil sample collection is carried out using different apparatus

and methods. The most appropriate container is a gas-tight glass

syringe of capacity 150 ml or 250 ml and fitted with three way

Teflon valves. The oil should retain and transport the sample of

transformer oil in the same condition as it is inside a transformer

with all fault gases dissolved in it. Attention to cleanliness is the

key to success. Oil samples shall be taken from the main oil

stream: points outside the main oil stream shall be disregarded.

This point should be located in a place where a live oil sample

can be collected rather than in an area where the oil is static. To

prevent oxidation the samples shall be shielded from direct light

by wrapping the container in aluminium foil or by storing in an

opaque enclosure.

Three samples have been collected. After doing the DGA

process of those oils, gas concentrations are found out. The

transformers from which oils have been collected are;

MSDS2/Transformer # 2 (132 kV/33 kV, 63 MVA)

CRM Transformer # 53 (33 kV/7.1 kV, 16 MVA)

Tandem mill rectifier transformer # 4 (33 kV/7.1 kV, 16

MVA)

III.DIAGNOSTIC METHODS OF DISSOLVED GASES

Different types of DGA methods have been

implemented in order to determine the fault in a transformer

which are analyzed as follows;

 Key gas method

 Ratios methods or Basic gas ratios method and

 National Standard’s method

 Duval Triangle method

Key gas method

Ratios methods or Basic gas ratios method

National Standard’s method

The Duval Triangle method

The Duval Triangle method, like any other DGA diagnostic

method, should be applied only when there is some suspicion of

a fault, based on an increase in combustible gas or some other

suspicious symptom. The diagnostic method itself is not a means

of fault detection. Because of the relative inaccuracy of gas-in- oil concentration measurements at low concentrations, DGA

diagnostic methods, including the Duval Triangle, should not be

Page 3 of 7

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 2020

applied unless the gas concentrations are well above the

detection limit.

The faults which are detected by Duval triangle are expressed as

follows;

 Partial Discharge (PD)

 Discharges of Low energy (D1)

 Discharges of High energy (D2)

 Thermal fault, (T1)

 Thermal fault, (T2)

 Thermal fault, (T3)

 Thermal & Electrical fault (DT)

IV.NOVEL METHODS FOR DETECTION OF DISSOLVED

GASES

Introduction

As discussed earlier the accurate knowledge of the

condition of transformers is essential for all electrical networks.

With the help of this information the maximized and expensive

failures can be avoided. As transformer is oil filled equipment

the DGA should give accurate, rapid and reliable results in the

field. So new technologies have been achieved to get extremely

high performance standards and genuine portability, giving

measurement of all the fault gases plus moisture. Infrared photo- acoustic spectroscopy (PAS) is such kind of the methods in

which the gases are extracted from the oil sample using highly

stable proprietary dynamic headspace equilibrium and then

measured.

Infrared Photo-Acoustic Spectroscopy for DGA

The conceptual design of a practical PAS measurement

module is shown in Figure. A simple hot wire source produces

broadband radiation across the IR range that is focused into the

measurement cell using a parabolic mirror. When a species

absorbs some of the incoming light, one of several mechanisms

of de-excitation is intermolecular colliding, which ultimately

leads to increases in translation energy of the gas particles —

that is, heating. According to the various gas laws, an increase in

the temperature of the gas leads to an increase in the pressure of

an isochoric (constant- volume) sample. The chopper wheel

rotates at a constant speed to give a modulated frequency light

signal from single to several thousand hertz

TRANSPORT X

The Kelman TRANSPORT X is a compact portable

Dissolved Gas Analysis (DGA) system which analyses oil

samples for all dissolved fault gases and moisture using infrared

photo-acoustic spectroscopy. If abnormal levels are detected, it

further provides a diagnostic using various IEEE/IEC approved

interpretation rules. The TRANSPORT X can also test direct gas

samples taken from transformer headspace or a Buchholz Relay.

The dynamic range of measurement and ability to have no

contamination between samples means it very suitable for

testing tap-changers and circuit breakers also

V.EXTENSION TO THE DUVAL TRIANGLE

The Duval triangle method previously discussed was

the classical Duval Triangle method for Transformers, Bushings

and cables filled with mineral oils. There are other triangles

analysed by Michael Duval, which are for Bio temperature oil,

FR#3 oil and silicon oil etc. For mineral oil he has also analysed

low temperature faults & faults in paper in mineral oils and

Thermal faults & faults in paper in mineral oils [16]. While the

previous method was giving the results with the value of the

concentration of methane, ethylene and acetylene; these analysis

give us more accurate information about the transformer taking

the concentration of other gases like hydrogen and ethane into

consideration.

It is an extension to the classical Duval triangle which gives

more specific information about the fault which is helpful for the

accurate analysis.

There are two such methods which are helpful to give more

details about the faults in a transformer, such as;

 Duval Triangle for low temperature faults & faults in

paper in mineral oils

 Duval Triangle for Thermal faults & faults in paper in

mineral oils

Duval Triangle for low temperature faults includes hydrogen,

methane and ethane for fault analysis while the Duval Triangle

for Thermal faults includes methane, ethylene and ethane for the

fault analysis.

Duval Triangle for low temperature faults & faults in paper in

mineral oils

This Duval triangle for low temperature faults in mineral oils

uses three gases for the analysis such as hydrogen, methane and

ethane. It is used to get more information about the faults

identified as low temperature faults i.e. PD, T1 and T2 as in

classical Duval Triangle. It should not be used for D1, D2 and

T3 as these are high temperature thermal faults but this triangle

is only helpful for low temperature faults.

There are five zones in this Duval triangle such as;

 PD- Corona partial discharge

 S- Stray gassing of mineral oil ( T < 200o C )

 C- Hot-spots with carbonization of paper

 O- Over-heating

 N/D- Not determined

In zone C, the probability of having carbonization of paper is 80

%.

Software Implementation

In software implementation of Duval triangle it is first required

to find out the coordinates of each zone and then it is applied in