Page 1 of 7

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 1998

A Fuzzy C- Means Clustering Algorithm for

Discrimination of Fault & Inrush Current in Power

Transformer

SAMANIDEESWARI.P

M.Tech – Power System Engineering,

PRIST Deemed University, Madurai, Tamilnadu

Abstract - However, the identification of the faulted location by

the traditional method is not always an easy task due to the

variability of gas data and operational natures. Incipient fault

detection in transformers can provide early warning of electrical

failure and could prevent catastrophic losses. To develop

transformer incipient fault detection technique, a transformer

model to simulate internal incipient faults is required. By

Improving high Performance the proposed new Algorithm is

Fuzzy C-Means Clustering for Identification of Inrush & Fault

current in the Power Transformer. This approach has the

advantages of high accuracy. The other advantage is that the

model is practically applicable and may be utilized for an

automated power transformer diagnosis. The test results indicate

that the developed preprocessing approach can significantly

improve the diagnosis accuracies for power transformer fault

classification. The algorithm is evaluated using simulation

performed with MATLAB.

Key Words: Fault Current , Inrush current, C- Means Clustering

I.INTRODUCTION

Large power transformers are probably the most

important equipment in an electrical system. Correct diagnosis

of their incipient faults is vital for safety and reliability of an

electrical network. An in-service transformer is subject to

electrical and thermal stresses, which can break down the

insulating materials and release gaseous decomposition products.

Overheating ,partial discharge and arcing are three primary

causes of fault related gases. There are many interpretative

methods based on DGA to diagnose the nature of transformer

deterioration. Stability and reliability of a power system in

depend upon the condition of power transformers. Essential

devices as power transformers are in a transmission and

distribution system. The wide varieties of electrical and thermal

stresses often age the transformers and subject them to incipient

faults. Being one of the most expensive and important elements,

a power transformers a highly essential element, whose failures

and damage may cause the outage of a power system. If an

incipient failure of a transformer is detected before it leads to a

catastrophic failure, predictive maintenance can be deployed to

minimize the risk of failures and further prevent loss of services.

To monitor the serviceability of power transformers, many

devices have evolved, such as Buchholz relays or differential

relays. But the main short coming of these devices is that they

only respond to the sever e power failures which require removal

of equipment from the service. Thus, techniques for early

detection of the faults would be very valuable to avoid outages

.In industrial practice, dissolved gas analysis (DGA) is a very

efficient tool for such purposes since it can warn about an

impending problem, provide an early diagnosis, and ensure

transformers maximum up time. To find out the incipient faults,

DGA is a prevailing method with periodically samples which

test the insulation oil of transformers to obtain the composition

of the gases dissolved in the oil due to the breakdown of the

insulating materials inside. Diverse diagnostic criteria were

developed for identification of the possible fault types by Rogers

ratios method and Doernenburg ratios method

This may improve and computerize transformer fault diagnosis.

By Improving high Performance the proposed new

Algorithm is Fuzzy C-Means Clustering for Identification of

Inrush & Fault current in the Power Transformer. This approach

Page 2 of 7

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 1999

has the advantages of high accuracy. The other advantage is that

the model is practically applicable and may be utilized for an

automated power transformer diagnosis. The test results indicate

that the developed preprocessing approach can significantly

improve the diagnosis accuracies for power transformer fault

classification. The algorithm is evaluated using simulation

performed with MATLAB

II.POWER TRANSFORMER FAILURES

Damages to the power transformer can be caused by

different stresses, which are due to overheating, open circuits

and short circuits. The major focus of power transformer

protection is short circuits because open circuits do not present a

particular hazard. Short circuit protection includes internal and

external faults.

External faults occur outside the protection zone of the

transformer and include:

 over voltage

 Overloads

 under frequency

Internal faults occur within the transformer protection zone. The

internal faults can be divided into two groups:

1. Incipient faults develop slowly and may develop into major

faults such as phase-to-ground faults or three phase faults if the

cause is not detected and corrected. Incipient faults can be

divided into three groups:

 Overheating

 Over fluxing

 Overpressure

2. Active faults – caused by the breakdown in insulation which

creates a sudden stress. The active fault occurs when the current

flows from one phase conductor to another such as phase-to- phase and phase-to-ground. These faults may occur suddenly

and they require fast action by protective relays. Active faults:

 Turn-to-turn short circuits.

 Phase-to-phase short circuits.

 Phase-to-ground short circuits.

 Tank faults.

 Core faults.

III.MAGNETIC INRUSH CONDITION

For the purposes of the discussion, inrush current is

described as the magnitude of instantaneous current drawn by a

line-frequency power transformer at the time the core is

energized; it’s of short duration, often milliseconds .Under a

combination of certain conditions, inrush current can be

measured at many times the rated load current. High inrush

current is a time-dependent phenomenon caused by a

coincidental set of circumstances that must occur simultaneously

at the moment of switch ON. Inrush current is a problem,

because it interferes with the operation of circuits as they have

been designed to function. In a digital world, there is a zero

tolerance for power interruptions. Some effects of high inrush

include nuisance fuse or breaker interruptions, as well as arcing

and failure of primary circuit components, such as switches.

High inrush currents also necessitate over sizing of fuses or

breakers, which complicates other aspects of approvals testing

and may compromise protection on other vital components.

Another side effect of high inrush is the injection of noise and

distortion back into the mains.

Fig-1 Graphical description of the inrush current phenomena

IV.PHYSICAL PROPERTIES OF INRUSH

Transformer inrush currents are drawn by the high

saturation of the iron core during the switching-in of the

transformer. Fig-1 illustrates a graphical description of the

inrush current phenomenon, while Fig.- 2shows that remanence

flux in the core at the moment of switch on increases inrush

current. Flux is generated as the results of applied voltage; it is

then cross-plotted with Φ-I characteristics to show the inrush

current magnitude. This practice is shown for two cases: with

Page 3 of 7

European Journal of Business &

Social Sciences

Available at https://ejbss.org/

ISSN: 2235-767X

Volume 07 Issue 04

April 2019

Available online: https://ejbss.org/ P a g e | 2000

and without resistance. The driving force of the inrush currents

is the voltage applied to the primary of the transformer. This

voltage forces the flux to build up to a maximum theoretical

value of double the steady-state flux plus remanence. Therefore,

the transformer is saturated and draws a large amount of current.

Since the current is of short duration, no adverse effects occur to

the transformer. However, the protective devices for overloads

may falsely operate and disconnect the transformer.

Fig- 2 Graphical description of inrush current phenomenon

including permanence.

V.DIAGNOSIS OF INCIPIENT FAULT

Importance of power transformer incipient fault diagnosis

Power transformers are major power system

equipment. Their reliability not only affects the electric energy

availability of the supplied area, but also affects the economical

operation of a utility. For example, the fault of a distribution

transformer may leave thousands of homes without heat and

light, and the fault of a step-up transformer in a power

generation plant may cause the shutdown of the attached

generation unit. Under the deregulation policy of electric

systems, each utility is trying to cut its cost, and the prevention

of accidental loss is much more important than before. The

capital loss of an accidental power transformer outage is often

counted in million dollars for output loss only, not to say the

costs associated with equipment repair or replacement. Because

of this economic incentive, preventive tests and on-line

monitoring are of benefit to predict incipient fault conditions,

and to schedule outage, maintenance and retirement of the

transformers.

Methodology of incipient fault diagnosis

The major concern of power transformer incipient

faults is that they may decrease the electrical and mechanical

integrity of the insulation system. This may progress to a point

that the insulation cannot withstand transient overstresses caused

by through-fault current (mechanical forces on windings) and

electrical over voltages (temporary, switching or lightning).

Incipient fault diagnosis is therefore closely related to insulation

condition assessment.

Insulation condition assessment test

Insulation condition assessment test refers mainly to

off-line routine tests, including measurement of insulation

resistance (IR), dielectric loss factor (DLF), interfacial

polarization(IP) using anomalous IR and frequency dispersion of

capacitance, turns ratio (TR), winding resistance (WR), core

ground resistance (CGR), and some excitation tests. These tests

are applied to the whole transformer and thus are bulk

measurements of the insulation condition. They can reveal some

severe problems but may not find the incipient ones. Other tests

examine paper or pressboard samples taken from transformers

(and which must be replaced if the transformer is to be returned

to service). These tests include measurement of the degree of

polymerization (DP) and tensile strength (TS). Some relatively

new methods, such as high performance liquid chromatography

(HPLC) furan analysis, interfacial polarization spectra (IPS)

using return voltage (RV) measurement, and analytical chemical

techniques , are also used for the same purpose. These intrusive

techniques are usually not favorable because the sampling

process may damage the integrity of the insulation system, but

may be necessary for very old transformers. The most favorable

tests for power transformer insulation assessment are on-line

types, including partial discharge (PD) monitoring and dissolved

gas-in-oil analysis (DGA). These online tests are also the major

incipient fault diagnosis methods.

Dissolved gas-in-oil analysis (DGA)

A more successful technique for on-line incipient fault

diagnosis is dissolved gas-in-oil analysis (DGA). By “on-line”

we mean the transformer does not need to be de-energized. This

type of analysis includes the conventional DGA, which is based

on routine oil sampling, and the modern technology of on-line

gas monitors. Conventional DGA has been in practice for about

thirty years, and has gained tremendous success compared to

other techniques. The main reason for this success is that the

sampling and analyzing procedures are simple and inexpensive,

and easy to be standardized. Many experiences have been gained

from the process and several DGA standards have been set up.